" Disconnection and reconnection of each phase of Transformer 330kV, 132kV, 11kV and 415 V connections
" Removal and disposal of the PCB contaminated oil from each single phase transformer.
" Total permanent in-situ repair / sealing of the tank lid gasket by welding of lid and sealing of bolts.
" Replacement of ALL gaskets on the Transformers, Coolers, Conservators, connecting pipes, accessories and diverter switch etc.
" Replacement / Repair of corroded steel parts and studs / pipes of the transformers Coolers and conservators connecting pipes and accessories.
" Repair of corroded sections on 330 kV bushing flanges.
" Refurbishment of oil pumps.
" Refurbishment of radiators
" Replace of diverter switch seals
" Dry out of transformer winding insulation
" Vacuum oil filling of each phase of the transformer, with new oil supplied by the Principal to site.
" Painting of all three single transformers
" Supply and Installation of Safety Platforms and hand rails in accordance with supplied information and sample drawings
" Complete replacement of six (6) fire door entries including fire certification.
" Modify 132 kV bushing connection to prevent expected bushing connection discharge damage.